Skip to main content

Appendix

Appendix A

FS10 Main Unit, Activating the aerosol generators

    Press both Activation buttons (1) for at least 3 seconds.

    The ventilation in the protected area is turned off.

    The activation delay time elapses. (0s-120s, set during commissioning). During this time the external release warning device is turned on, the internal buzzer is bleeping and the Activate indicator (6) is blinking. It is possible to hold the activation by pressing or holding the Hold button (2). Activation will be hold while the button is pressed down. Activation delay “countdown” continues when releasing the button. Activation will be aborted if the Hold Button is pressed for more than 20 seconds.

    The aerosol generators are activated.

    After activation the internal buzzer and the Activate indicator (6) are turned on permanently. The internal buzzer may be turned off by pressing the Mute / Reset button (11).

    After complete extinction of fire, the ventilation in the protected area may be restarted by pressing the Restart Ventilation button (2).

    Fire alarm handling – Manual mode

      If the required detector inputs are in alarm state (set during commissioning), the internal buzzer and external fire alarm device is turned on.

      The internal buzzer and external fire alarm device may be turned off by pressing the Mute / Reset button (11).

      If deemed necessary, the aerosol generators may be activated to extinguish the fire. Do this by pressing both the Activation buttons (1) for > 3 seconds as described above.

      When the fire or smoke is no longer present, the fire alarm may be reset by pressing the pressing the Mute / Reset Detector button (11).

      Fire alarm handling – Automatic mode

        If the required detector inputs are in alarm state (set during commissioning), the internal buzzer and external fire alarm device is turned on, and delay time is activated before the aerosol generators is released. See section 4 for instructions on activation. See section 5 for instructions on fire alarm handling.

        Appendix B

        FS10 Remote Panel

        image8.pngThis Appendix provides operational guidance for the FS10 Remote Panel for the FS10 system.

        SYSTEM OVERVIEW

        System Purpose

        The FS10 Remote Panel is a remote control and monitoring unit for the FS10 System.

        System description

        The purpose of the FS10 Remote Panel is to have a slim, smooth and more elegant panel for bridges or a like. It is connected to the FS10 Main Unit, which can be mounted just outside the protected area.

        Every relevant info for the FS10 system is shown, and action can be taken on the front of the FS10 Remote Panel.

        Main System Functions

          Connected to the FS10 Main Unit by a 4-wired cable, the FS10 Remote Panel are able to:

            Continuous system supervision.

            Fire alarm detection.

            Manual and automatic activation.

            Activation delay sequence.

            Warning outputs.

            Ventilation relay control.

            System fault indication.

            Dual power input monitoring.

            Event logging.

            System Components

              Connected to the FS10 Main Unit – and units connected to that.

              CONTROLS AND INDICATORS

              Remote Panel Overview, Front

              Et billede, der indeholder tekst, skærmbillede, diagram, elektronik AI-genereret indhold kan være ukorrekt.

              Indicators and buttons

                Press Both to Activate

                Press the two buttons in the middle at the same time for 3sec. to release the FS10 system. The pre-programmed delay time, before release, will start, and the internal buzzer will be beeping, and steady when released.

                  Hold / Restart Button

                  This button has four functions.

                    HOLD: Press to hold the delay time when the FS10 is activated for release. Press 20sec to cancel an activation.

                    ISOLATE: Press 3 sec. to activate isolation mode to the aerosol generator.

                    RESTART: Press to re-start the ventilation in the protected area, after the FS10 system has been released.

                    To make a lamptest, press and hold button for > 3 sec.

                    **

                      Mode Button

                      Press MODE to change from manual to automatic release if it is set available during configuration.

                        Mute / Reset Button

                          Press the MUTE / RESET button to mute the internal buzzer when a fault occurs.

                          Press the MUTE / RESET button to reset fault indicator, when it is ok again.

                          For lamp test press the MUTE / RESET button for 3sec.

                            System OK indicator

                            When the FS10 system is powered up without any fault, the SYSTEM OK will be steady green.

                              Hold / Isolate indicator

                              Will be steady orange when HOLD or ISOLATE mode is activated.

                                Manual Mode and Automatic Mode Indicators

                                Will be green and show whether MANUAL or AUTOMAIC mode is chosen

                                Press MODE to change from manual to automatic release if it is set available during configuration.

                                  Fault indicator

                                  The fault indicator (red) turns on if any fault occurs on the FS10 system

                                  Press MODE to change from manual to automatic release if it is set available during configuration.

                                    Activated indicator

                                    The ACTIVATED indicator (orange) will be flashing in the pre-programmed delay time before release. And steady when released.

                                      Fire Alarm indicator

                                      The FIRE ALARM indicator will be on if the devices connected to the detector input are active on the FS10 system.

                                        Photo diode

                                        Will dimmer the LEDs on the FS10 Remote panel when the dark is coming.

                                        Appendix C

                                        FS10 External Activation Switch

                                        FS10 External Activation Switch makes it possible to activate the Aerosol Generators without having direct access to the FS10 panel. For example, it can be placed just outside the protected area where it must be possible to activate the Aerosol Generators.

                                        Et billede, der indeholder elektronik, tekst, gadget, Elektronisk enhed Automatisk genereret beskrivelse
                                          *Open Lid and press the button* Open lid and press the button to Activate the Aerosol Generators. The pre-programmed delay time, before release, will start At the FS10 Main Unit the LED for Activation will be lid and the internal buzzer will be beeping, and steady when released.

                                          Appendix D

                                          FS10 External Isolation Switch

                                          FS10 External Isolation Switch makes it possible to activate “ISOLATE” or “HOLD” mode without having direct access to the FS10.

                                          Due to safety distance from the Aerosol Generators, we recommend to place an External Isolation Switch just outside the protected area, making it possible to Isolate the Aerosol Generators before entering the protected area – and to “de-isolate” when leaving again.

                                          The ON LED will be green when system is ON, and the ISO LED will be yellow when the system is isolated

                                          Et billede, der indeholder kamera, elektronik, Elektronisk enhed, gadget Automatisk genereret beskrivelse
                                            Hold / Isolate Button

                                            This button has three functions.

                                              HOLD: Press to hold the delay time when the FS10 is activated for release Press 20sec to cancel an activation

                                              ISOLATE: Press 3sec to activate isolate mode to the aerosol generator

                                              RESTART: Press to re-start the ventilation in the protected area, after the FS10 system has been released

                                              At the FS10 Main Unit the LED for Hold´/ Isolate will be lid.

                                              Appendix E

                                              FS10 Connection Box

                                              Et billede, der indeholder elektronik, Elektroteknik, maskine, Elarbejde Automatisk genereret beskrivelseFS10 Connection Box makes sense when you have multiple Aerosol Generators attached to the FS10.

                                              In this way you can save on the use of cable, and it makes the mounting in the FS10 easier.

                                              Et billede, der indeholder tekst, Elektronisk enhed, elektronik, gadget Automatisk genereret beskrivelse