Fire Alarm Operation
Fire Detection
-
Fire LED (red).
-
Buzzer active.
-
Fire relay active.
Automatic Activation Sequence (if enabled)
-
Fire detected.
-
Activation delay begins.
-
Activation LED blinks.
-
Warning devices activate.
-
Aerosol discharge occurs after delay.
Manual Activation Procedure
-
Press and hold both activation buttons simultaneously for ≥ 3 seconds.
-
Activation delay begins.
-
Activation LED blinks.
-
Warning devices activate.
-
Aerosol discharge occurs after delay.
Hold/Cancel
-
Delay time can be hold if button is pressed.
-
Cancel activation by pressing button ≥ 20 seconds.
Ventilation Shutdown and Restart
-
Ventilation OFF during activation.
-
Restart ventilation manually when safe.
After a Fire Event
-
Restart ventilation.
-
Confirm fire extinguished.
-
Technician inspection required.
Sticker, user quick guide
-
The sticker, enclosed to the FS10 Main Unit, gives a quick introduction to the user of the FS10 Main Unit.
-
It is recommended to setup the sticker next to the FS10 Main Unit, making all able to use the FS10 Main Unit in an emergency situation.
-
Sticker: