SYSTEM OVERVIEW

System Purpose

The FS10 Remote Panel is a remote control and monitoring unit for the FS10 System.

System description

The purpose of the FS10 Remote Panel is to have a slim, smooth and more elegant panel for bridges or a like. It is connected to the FS10 Main Unit, which can be mounted just outside the protected area.

Every relevant info for the FS10 system is shown, and action can be taken on the front of the FS10 Remote Panel.

Main System Functions

System Components

CONTROLS AND INDICATORS

Remote Panel Overview, Front

Et billede, der indeholder tekst, skærmbillede, diagram, elektronik AI-genereret indhold kan være ukorrekt.

Indicators and buttons

  1. Press Both to Activate

Press the two buttons in the middle at the same time for 3sec. to release the FS10 system. The pre-programmed delay time, before release, will start, and the internal buzzer will be beeping, and steady when released.

  1. Hold / Restart Button

This button has four functions.

**

  1. Mode Button

Press MODE to change from manual to automatic release if it is set available during configuration.

  1. Mute / Reset Button
  1. System OK indicator

When the FS10 system is powered up without any fault, the SYSTEM OK will be steady green.

  1. Hold / Isolate indicator

Will be steady orange when HOLD or ISOLATE mode is activated.

  1. Manual Mode and Automatic Mode Indicators

Will be green and show whether MANUAL or AUTOMAIC mode is chosen

Press MODE to change from manual to automatic release if it is set available during configuration.

  1. Fault indicator

The fault indicator (red) turns on if any fault occurs on the FS10 system

Press MODE to change from manual to automatic release if it is set available during configuration.

  1. Activated indicator

The ACTIVATED indicator (orange) will be flashing in the pre-programmed delay time before release. And steady when released.

  1. Fire Alarm indicator

The FIRE ALARM indicator will be on if the devices connected to the detector input are active on the FS10 system.

  1. Photo diode

Will dimmer the LEDs on the FS10 Remote panel when the dark is coming.

Appendix C

FS10 External Activation Switch

FS10 External Activation Switch makes it possible to activate the Aerosol Generators without having direct access to the FS10 panel. For example, it can be placed just outside the protected area where it must be possible to activate the Aerosol Generators.

Et billede, der indeholder elektronik, tekst, gadget, Elektronisk enhed Automatisk genereret beskrivelse
  1. *Open Lid and press the button* Open lid and press the button to Activate the Aerosol Generators. The pre-programmed delay time, before release, will start At the FS10 Main Unit the LED for Activation will be lid and the internal buzzer will be beeping, and steady when released.

Appendix D

FS10 External Isolation Switch

FS10 External Isolation Switch makes it possible to activate “ISOLATE” or “HOLD” mode without having direct access to the FS10.

Due to safety distance from the Aerosol Generators, we recommend to place an External Isolation Switch just outside the protected area, making it possible to Isolate the Aerosol Generators before entering the protected area – and to “de-isolate” when leaving again.

The ON LED will be green when system is ON, and the ISO LED will be yellow when the system is isolated

Et billede, der indeholder kamera, elektronik, Elektronisk enhed, gadget Automatisk genereret beskrivelse
  1. Hold / Isolate Button

This button has three functions.

At the FS10 Main Unit the LED for Hold´/ Isolate will be lid.

Appendix E

FS10 Connection Box

Et billede, der indeholder elektronik, Elektroteknik, maskine, Elarbejde Automatisk genereret beskrivelseFS10 Connection Box makes sense when you have multiple Aerosol Generators attached to the FS10.

In this way you can save on the use of cable, and it makes the mounting in the FS10 easier.

Et billede, der indeholder tekst, Elektronisk enhed, elektronik, gadget Automatisk genereret beskrivelse

Revision #2
Created 2026-04-29 11:09:29 CEST by Admin
Updated 2026-04-29 11:10:51 CEST by Admin